       Size Dimensions and Ratings


    


Nonimal
Cross Sectional
Area of Conductor

Sq.mm


   Number/Nom.
   Dia of Wires
    ( Nom )

     Number/mm

Thickness of insulation
( Nom)

    mm


Overall
Diameter
Max.

     mm

  Current Rating

D.C Resistance
( Max.) at20oC

Ohm/Km

Casing
Amps

Concealed
Amps
   0.75
        24/0.2
         0.6
      2.8
     8.00
      7.00
    26.00
  1.00
        32/0.2
         0.6
      3.0
  12.00
    11.00
    19.50
  1.50
        30/0.25
         0.7
      3.4
  16.00
    13.00
    13.30
  2.50
        50/0.25
         0.8
      4.1
  22.00
    18.00
      7.98
  4.00
        56/0.3
         0.8
      4.8
  29.00
     24.00
      4.95
  6.00
        84/0.3
         0.8
      5.3
  37.00
     31.00
      3.30